Skip to Content

Brine cooler EA-G-480GE4-A01 C

Brine cooler EA-G-480GE4-A01 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-480GE4-A01 C

Cooling capacity i
141.79 kW
Air flow
73,055 m³/h
Fin spacing
4.6 mm
Air throw
41 m
Fans
4 × ⌀800 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 73,055 m³/h
Air throw 41 m
External surface 781.9 m²
Inner volume 163.1 dm³
Fin spacing 4.6 mm
Fin materialAluminium
Net weight 718 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 63.0 dB(A)
Sound power 86.8 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
EA-G-480GE4-A01 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
141.789 kW Sensible capacity 102.455 kW Fluid flow 44.54 m³/h Pressure drop 127.6 kPa above the recommended pressure drop
Cooling capacity · Low speed (Y)
115.831 kW Sensible capacity 83.423 kW Fluid flow 36.37 m³/h Pressure drop 89.0 kPa above the recommended pressure drop

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated ≈ 26.88 ≈ 27.20 ≈ 50.84 56.25
8 not rated not rated not rated not rated ≈ 89.34 ≈ 95.05 ≈ 102.18 110.83
10 not rated not rated not rated not rated 135.24 141.79 149.85 162.76
12 not rated not rated not rated not rated not rated 184.64 196.30 212.31

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 25.00 ≈ 24.84 ≈ 24.95 ≈ 43.79
8 not rated not rated not rated not rated ≈ 41.48 ≈ 76.06 ≈ 83.44 ≈ 92.16
10 not rated not rated not rated not rated ≈ 108.52 115.83 123.78 135.10
12 not rated not rated not rated not rated not rated 151.12 161.96 175.78

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 141.789 44.54 127.6
Low speed (Y) 115.831 36.37 89.0

Dimensions

Dimension drawing of EA-G-480GE4-A01 C
Dimension drawing
Dimensions as drawn
A 5615 mm
B 1050 mm
C 1430 mm
F 1010 mm
G 1115 mm
E1 1318 mm
E2 1300 mm
E 5235 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5615 mm
Width 1050 mm
Height 1430 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.