Skip to Content

Brine cooler EA-G-663EE4-A11 C

Brine cooler EA-G-663EE4-A11 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-663EE4-A11 C

Cooling capacity i
130.36 kW
Air flow
83,013 m³/h
Fin spacing
4.6 mm
Air throw
43 m
Fans
6 × ⌀630 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 83,013 m³/h
Air throw 43 m
External surface 601.5 m²
Inner volume 135.3 dm³
Fin spacing 4.6 mm
Fin materialAluminium
Net weight 530 kg
Fans
Quantity 6
Diameter 630 mm
Speed 1,330 rpm
Power 15,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 75.0 dB(A)
Sound power 98.4 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
EA-G-663EE4-A11 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
130.355 kW Sensible capacity 94.713 kW Fluid flow 40.94 m³/h Pressure drop 129.9 kPa above the recommended pressure drop
Cooling capacity · Low speed (Y)
111.327 kW Sensible capacity 80.589 kW Fluid flow 34.96 m³/h Pressure drop 98.2 kPa above the recommended pressure drop

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated ≈ 22.50 ≈ 22.79 ≈ 48.08 52.89
8 not rated not rated not rated not rated ≈ 82.03 ≈ 86.31 93.95 100.36
10 not rated not rated not rated not rated 124.93 130.36 137.19 149.19
12 not rated not rated not rated not rated not rated 170.96 181.10 195.79

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated ≈ 21.13 ≈ 21.36 ≈ 21.49 ≈ 43.65
8 not rated not rated not rated not rated ≈ 65.09 ≈ 72.67 ≈ 79.42 86.85
10 not rated not rated not rated not rated 105.40 111.33 118.18 129.03
12 not rated not rated not rated not rated not rated 146.19 155.96 169.08

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 130.355 40.94 129.9
Low speed (Y) 111.327 34.96 98.2

Dimensions

Dimension drawing of EA-G-663EE4-A11 C
Dimension drawing
Dimensions as drawn
A 5215 mm
B 1000 mm
C 1190 mm
F 960 mm
E1 818 mm
E2 800 mm
E 4835 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5215 mm
Width 1000 mm
Height 1190 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.