EA-G-480GG7-A01 C
130.74 kW
Defrost: None
Product code: EA-G-663EE4-A11 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 83,013 m³/h |
|---|---|
| Air throw | 43 m |
| External surface | 601.5 m² |
| Inner volume | 135.3 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 530 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 15,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 98.4 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| EA-G-663EE4-A11 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | ≈ 22.50 | ≈ 22.79 | ≈ 48.08 | 52.89 |
| 8 | not rated | not rated | not rated | not rated | ≈ 82.03 | ≈ 86.31 | 93.95 | 100.36 |
| 10 | not rated | not rated | not rated | not rated | 124.93 | 130.36 | 137.19 | 149.19 |
| 12 | not rated | not rated | not rated | not rated | not rated | 170.96 | 181.10 | 195.79 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | ≈ 21.13 | ≈ 21.36 | ≈ 21.49 | ≈ 43.65 |
| 8 | not rated | not rated | not rated | not rated | ≈ 65.09 | ≈ 72.67 | ≈ 79.42 | 86.85 |
| 10 | not rated | not rated | not rated | not rated | 105.40 | 111.33 | 118.18 | 129.03 |
| 12 | not rated | not rated | not rated | not rated | not rated | 146.19 | 155.96 | 169.08 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 130.355 | 40.94 | 129.9 |
| Low speed (Y) | 111.327 | 34.96 | 98.2 |
| A | 5215 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 4835 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5215 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.