EA-G-563FG4-A19 C
127.17 kW
Defrost: None
Product code: EA-G-480GD4-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 77,315 m³/h |
|---|---|
| Air throw | 43 m |
| External surface | 651.6 m² |
| Inner volume | 134.6 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 676 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-480GD4-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | ≈ 23.09 | ≈ 23.34 | ≈ 46.96 | 51.16 |
| 8 | not rated | not rated | not rated | not rated | ≈ 81.61 | ≈ 85.31 | 91.83 | 98.63 |
| 10 | not rated | not rated | not rated | not rated | 121.93 | 126.98 | 133.77 | 145.22 |
| 12 | not rated | not rated | not rated | not rated | not rated | 165.54 | 175.59 | 189.74 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 21.41 | ≈ 21.51 | ≈ 21.62 | ≈ 40.80 |
| 8 | not rated | not rated | not rated | not rated | ≈ 35.73 | ≈ 69.70 | ≈ 75.69 | ≈ 82.92 |
| 10 | not rated | not rated | not rated | not rated | ≈ 99.50 | 105.24 | 111.92 | 121.93 |
| 12 | not rated | not rated | not rated | not rated | not rated | 137.37 | 146.69 | 158.99 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 126.982 | 39.87 | 149.6 |
| Low speed (Y) | 105.239 | 33.04 | 107.0 |
| A | 5615 mm |
|---|---|
| B | 1000 mm |
| C | 1430 mm |
| F | 960 mm |
| G | 1065 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 5235 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 5615 mm |
|---|---|
| Width | 1000 mm |
| Height | 1430 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.