Skip to Content

Brine cooler EA-G-563FE4-A08 C

Brine cooler EA-G-563FE4-A08 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-563FE4-A08 C

Cooling capacity i
123.23 kW
Air flow
69,691 m³/h
Fin spacing
4.6 mm
Air throw
41 m
Fans
5 × ⌀630 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 69,691 m³/h
Air throw 41 m
External surface 626.5 m²
Inner volume 131.4 dm³
Fin spacing 4.6 mm
Fin materialAluminium
Net weight 524 kg
Fans
Quantity 5
Diameter 630 mm
Speed 1,340 rpm
Power 9,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 75.0 dB(A)
Sound power 99.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
EA-G-563FE4-A08 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
123.234 kW Sensible capacity 89.259 kW Fluid flow 38.70 m³/h Pressure drop 128.3 kPa above the recommended pressure drop
Cooling capacity · Low speed (Y)
105.877 kW Sensible capacity 76.455 kW Fluid flow 33.24 m³/h Pressure drop 98.0 kPa above the recommended pressure drop

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated ≈ 22.42 ≈ 22.66 ≈ 44.57 49.34
8 not rated not rated not rated not rated ≈ 77.57 ≈ 82.03 88.25 95.81
10 not rated not rated not rated not rated 117.91 123.23 130.13 141.65
12 not rated not rated not rated not rated not rated 161.09 171.24 185.42

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 21.04 ≈ 21.25 ≈ 21.36 ≈ 41.03
8 not rated not rated not rated not rated ≈ 35.22 ≈ 69.57 ≈ 76.32 ≈ 83.29
10 not rated not rated not rated not rated ≈ 99.92 105.88 112.69 122.97
12 not rated not rated not rated not rated not rated 138.57 148.06 160.67

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 123.234 38.70 128.3
Low speed (Y) 105.877 33.24 98.0

Dimensions

Dimension drawing of EA-G-563FE4-A08 C
Dimension drawing
Dimensions as drawn
A 5415 mm
B 1000 mm
C 1190 mm
F 960 mm
G 1035 mm
E1 1018 mm
E2 1000 mm
E 5035 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5415 mm
Width 1000 mm
Height 1190 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.