EA-G-663ED4-A11 C
115.21 kW
Defrost: None
Product code: EA-G-480GG10-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
How to read the code of this model.
| Air flow | 75,961 m³/h |
|---|---|
| Air throw | 43 m |
| External surface | 507.8 m² |
| Inner volume | 212.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 763 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 86.1 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| EA-G-480GG10-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 29.61 | 29.00 | ≈ 29.09 | ≈ 29.04 |
| 8 | not rated | not rated | not rated | not rated | 48.53 | ≈ 45.92 | ≈ 83.83 | ≈ 92.50 |
| 10 | not rated | not rated | not rated | not rated | ≈ 68.28 | 115.42 | 125.33 | 138.01 |
| 12 | not rated | not rated | not rated | not rated | not rated | 153.36 | 165.54 | 180.46 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 27.16 | 26.00 | 26.04 | ≈ 25.94 |
| 8 | not rated | not rated | not rated | not rated | 44.01 | ≈ 41.08 | ≈ 41.00 | ≈ 75.81 |
| 10 | not rated | not rated | not rated | not rated | ≈ 61.42 | 91.49 | ≈ 102.72 | 114.14 |
| 12 | not rated | not rated | not rated | not rated | not rated | 124.31 | 136.18 | 149.36 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 115.415 | 36.25 | 56.6 |
| Low speed (Y) | 91.487 | 28.74 | 37.4 |
| A | 5615 mm |
|---|---|
| B | 1150 mm |
| C | 1430 mm |
| F | 1110 mm |
| G | 1215 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 5235 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5615 mm |
|---|---|
| Width | 1150 mm |
| Height | 1430 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.