EA-G-363GE4-A19 C
63.69 kW
Defrost: None
Product code: EA-G-563ED4-A06 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 40,567 m³/h |
|---|---|
| Air throw | 24 m |
| External surface | 417.7 m² |
| Inner volume | 91.7 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 417 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 3,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 80.4 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| EA-G-563ED4-A06 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 14.13 | 14.28 | ≈ 14.36 | ≈ 14.38 |
| 8 | not rated | not rated | not rated | not rated | 23.63 | ≈ 23.05 | ≈ 44.51 | ≈ 50.57 |
| 10 | not rated | not rated | not rated | not rated | ≈ 33.78 | 63.76 | 70.22 | 78.44 |
| 12 | not rated | not rated | not rated | not rated | not rated | 87.13 | 94.84 | 104.32 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 13.31 | 13.27 | ≈ 13.33 | ≈ 13.30 |
| 8 | not rated | not rated | not rated | not rated | 22.09 | ≈ 21.17 | ≈ 35.12 | ≈ 42.59 |
| 10 | not rated | not rated | not rated | not rated | ≈ 31.37 | 52.01 | 59.21 | 66.64 |
| 12 | not rated | not rated | not rated | not rated | not rated | 72.86 | 80.27 | 88.59 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 63.762 | 20.03 | 44.2 |
| Low speed (Y) | 52.010 | 16.33 | 30.8 |
| A | 4415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 4035 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4415 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.