EA-G-363GE4-A19 C
63.69 kW
Defrost: None
Product code: EA-G-663ED7-A06 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 51,466 m³/h |
|---|---|
| Air throw | 26 m |
| External surface | 338.0 m² |
| Inner volume | 116.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 458 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 81.1 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| EA-G-663ED7-A06 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 15.22 | 15.21 | ≈ 15.27 | ≈ 15.29 |
| 8 | not rated | not rated | not rated | not rated | 25.20 | ≈ 24.34 | ≈ 45.36 | ≈ 50.31 |
| 10 | not rated | not rated | not rated | not rated | ≈ 35.69 | 63.65 | 68.90 | 76.11 |
| 12 | not rated | not rated | not rated | not rated | not rated | 85.21 | 91.80 | 100.25 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 14.40 | 14.15 | ≈ 14.19 | ≈ 14.19 |
| 8 | not rated | not rated | not rated | not rated | 23.65 | ≈ 22.47 | ≈ 38.58 | ≈ 43.83 |
| 10 | not rated | not rated | not rated | not rated | ≈ 33.33 | 54.35 | 59.99 | 66.62 |
| 12 | not rated | not rated | not rated | not rated | not rated | 73.69 | 80.16 | 87.72 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 63.649 | 19.99 | 50.1 |
| Low speed (Y) | 54.353 | 17.07 | 38.0 |
| A | 5215 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 4835 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5215 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.