EA-G-563FG7-A19 C
99.62 kW
Defrost: None
Product code: EA-G-563EE4-A11 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 69,212 m³/h |
|---|---|
| Air throw | 42 m |
| External surface | 501.2 m² |
| Inner volume | 107.6 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 448 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 13,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 74.0 dB(A) |
|---|---|
| Sound power | 97.4 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| EA-G-563EE4-A11 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 18.75 | ≈ 18.99 | ≈ 19.13 | ≈ 37.52 |
| 8 | not rated | not rated | not rated | not rated | ≈ 31.01 | ≈ 58.16 | ≈ 70.35 | ≈ 76.93 |
| 10 | not rated | not rated | not rated | not rated | ≈ 91.57 | 99.70 | 106.98 | 118.13 |
| 12 | not rated | not rated | not rated | not rated | not rated | 134.16 | 143.85 | 157.03 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 17.61 | 17.80 | ≈ 17.91 | ≈ 17.96 |
| 8 | not rated | not rated | not rated | not rated | ≈ 29.33 | ≈ 28.86 | ≈ 58.93 | ≈ 66.19 |
| 10 | not rated | not rated | not rated | not rated | ≈ 73.63 | 84.30 | 91.85 | 102.08 |
| 12 | not rated | not rated | not rated | not rated | not rated | 114.29 | 123.71 | 135.56 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 99.701 | 31.31 | 72.4 |
| Low speed (Y) | 84.295 | 26.47 | 53.8 |
| A | 4415 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 4035 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4415 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.