EA-G-563FG7-A19 C
99.62 kW
Defrost: None
Product code: EA-G-663EE7-A11 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 89,076 m³/h |
|---|---|
| Air throw | 46 m |
| External surface | 405.6 m² |
| Inner volume | 135.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 491 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 15,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 74.0 dB(A) |
|---|---|
| Sound power | 98.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| EA-G-663EE7-A11 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 20.31 | ≈ 20.52 | ≈ 20.65 | ≈ 39.37 |
| 8 | not rated | not rated | not rated | not rated | ≈ 33.53 | ≈ 62.66 | ≈ 71.03 | 76.57 |
| 10 | not rated | not rated | not rated | not rated | ≈ 93.28 | 99.05 | 105.09 | 114.98 |
| 12 | not rated | not rated | not rated | not rated | not rated | 131.07 | 139.45 | 151.36 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 18.98 | ≈ 19.19 | ≈ 19.29 | ≈ 31.73 |
| 8 | not rated | not rated | not rated | not rated | ≈ 31.56 | ≈ 50.66 | ≈ 60.88 | ≈ 66.41 |
| 10 | not rated | not rated | not rated | not rated | ≈ 77.75 | 84.91 | 91.02 | 99.93 |
| 12 | not rated | not rated | not rated | not rated | not rated | 112.91 | 120.89 | 131.48 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 99.047 | 31.11 | 79.9 |
| Low speed (Y) | 84.911 | 26.67 | 60.9 |
| A | 5215 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 4835 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5215 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.