EA-G-563FC4-A19 C
81.39 kW
Defrost: None
Product code: EA-G-563FD7-A08 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 76,603 m³/h |
|---|---|
| Air throw | 45 m |
| External surface | 352.1 m² |
| Inner volume | 108.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 449 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 9,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-563FD7-A08 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 17.09 | ≈ 17.24 | ≈ 17.33 | ≈ 32.31 |
| 8 | not rated | not rated | not rated | not rated | ≈ 28.30 | ≈ 52.00 | ≈ 58.52 | 63.21 |
| 10 | not rated | not rated | not rated | not rated | ≈ 76.92 | 81.44 | 86.42 | 94.60 |
| 12 | not rated | not rated | not rated | not rated | not rated | 107.48 | 114.44 | 124.34 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 16.15 | ≈ 16.23 | ≈ 16.31 | ≈ 26.88 |
| 8 | not rated | not rated | not rated | not rated | ≈ 26.81 | ≈ 43.69 | ≈ 51.30 | ≈ 55.95 |
| 10 | not rated | not rated | not rated | not rated | ≈ 65.93 | 71.38 | 76.39 | 83.83 |
| 12 | not rated | not rated | not rated | not rated | not rated | 94.55 | 101.21 | 110.12 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 81.442 | 25.58 | 86.9 |
| Low speed (Y) | 71.376 | 22.42 | 68.8 |
| A | 5415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| G | 985 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 5415 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.