EA-HL-G-450AC7-A10 C
39.26 kW
Defrost: None
Product code: EA-HL-G-350AG10-A10 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 22,168 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 139.1 m² |
| Inner volume | 64.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 279 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 2,070 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 85.1 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-HL-G-350AG10-A10 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 13.80 | 12.13 | ≈ 12.09 | ≈ 12.09 |
| 8 | not rated | not rated | not rated | not rated | 22.02 | ≈ 20.92 | ≈ 29.62 | ≈ 35.41 |
| 10 | not rated | not rated | not rated | not rated | ≈ 30.36 | 41.71 | 46.66 | 52.01 |
| 12 | not rated | not rated | not rated | not rated | not rated | 55.28 | 61.00 | 67.40 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 12.70 | 11.26 | 10.98 | ≈ 10.96 |
| 8 | not rated | not rated | not rated | not rated | 20.09 | 19.20 | ≈ 18.86 | ≈ 30.29 |
| 10 | not rated | not rated | not rated | not rated | 27.54 | 27.20 | ≈ 39.88 | 44.82 |
| 12 | not rated | not rated | not rated | not rated | not rated | 46.89 | 52.38 | 58.10 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 41.706 | 13.10 | 66.0 |
| Low speed (Y) | 27.196 | 8.54 | 30.9 |
| A | 3387 mm |
|---|---|
| B | 740 mm |
| C | 875 mm |
| F | 660 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 3035 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3387 mm |
|---|---|
| Width | 740 mm |
| Height | 875 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.