EA-HL-G-250AG4-A10 C
39.16 kW
Defrost: None
Product code: EA-HL-G-450AC7-A10 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 31,975 m³/h |
|---|---|
| Air throw | 25 m |
| External surface | 127.2 m² |
| Inner volume | 45.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 254 kg |
| Quantity | 4 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 2,760 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-HL-G-450AC7-A10 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 9.76 | 9.51 | ≈ 9.57 | ≈ 9.61 |
| 8 | not rated | not rated | not rated | not rated | 16.06 | ≈ 15.15 | ≈ 28.38 | ≈ 32.33 |
| 10 | not rated | not rated | not rated | not rated | ≈ 22.67 | 39.26 | 43.44 | 48.55 |
| 12 | not rated | not rated | not rated | not rated | not rated | 52.38 | 57.51 | 63.66 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 9.27 | 8.92 | ≈ 8.97 | ≈ 9.00 |
| 8 | not rated | not rated | not rated | not rated | 15.16 | ≈ 14.16 | ≈ 24.30 | ≈ 28.64 |
| 10 | not rated | not rated | not rated | not rated | ≈ 21.28 | 34.16 | 38.43 | 43.19 |
| 12 | not rated | not rated | not rated | not rated | not rated | 46.10 | 51.03 | 56.63 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 39.256 | 12.33 | 79.3 |
| Low speed (Y) | 34.158 | 10.73 | 62.0 |
| A | 4387 mm |
|---|---|
| B | 590 mm |
| C | 875 mm |
| F | 510 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 4035 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 4387 mm |
|---|---|
| Width | 590 mm |
| Height | 875 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.