Skip to Content

Brine cooler EA-HL-G-450AC10-A10 C

Brine cooler EA-HL-G-450AC10-A10 C
Illustrative photo

Producer: Karyer · Line: EA-HL-G (High Type)

Product code: EA-HL-G-450AC10-A10 C

Cooling capacity i
30.03 kW
Air flow
32,513 m³/h
Fin spacing
10.0 mm
Air throw
25 m
Fans
4 × ⌀500 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 32,513 m³/h
Air throw 25 m
External surface 93.1 m²
Inner volume 45.6 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 247 kg
Fans
Quantity 4
Diameter 500 mm
Speed 1,360 rpm
Power 2,760 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 64.0 dB(A)
Sound power 87.0 dB(A)
Energy class E
Connections
Inlet 2"
Outlet 2"
Defrost
EA-HL-G-450AC10-A10 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
30.034 kW Sensible capacity 22.127 kW Fluid flow 9.43 m³/h Pressure drop 49.4 kPa
Cooling capacity · Low speed (Y)
18.374 kW Sensible capacity 13.626 kW Fluid flow 5.77 m³/h Pressure drop 20.7 kPa

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 8.82 8.45 8.50 ≈ 8.54
8 not rated not rated not rated not rated 14.37 ≈ 13.45 ≈ 13.50 ≈ 25.68
10 not rated not rated not rated not rated ≈ 20.12 30.03 ≈ 34.60 39.25
12 not rated not rated not rated not rated not rated 41.46 46.31 51.66

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 8.35 7.91 7.95 ≈ 7.97
8 not rated not rated not rated not rated 13.52 12.72 ≈ 12.68 ≈ 22.64
10 not rated not rated not rated not rated 18.84 18.37 ≈ 30.59 35.02
12 not rated not rated not rated not rated not rated 36.39 41.20 46.15

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 30.034 9.43 49.4
Low speed (Y) 18.374 5.77 20.7

Dimensions

Dimension drawing of EA-HL-G-450AC10-A10 C
Dimension drawing
Dimensions as drawn
A 4387 mm
B 590 mm
C 875 mm
F 510 mm
E1 1018 mm
E2 1000 mm
E 4035 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 4387 mm
Width 590 mm
Height 875 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.