ED-G-450AE4-A21 C
64.84 kW
Defrost: None
Product code: ED-G-363AG4-A27 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 23,138 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 479.7 m² |
| Inner volume | 91.1 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 398 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 79.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| ED-G-363AG4-A27 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 16.84 | ≈ 15.37 | ≈ 15.42 | ≈ 25.08 |
| 8 | not rated | not rated | not rated | not rated | ≈ 27.55 | ≈ 45.29 | ≈ 48.54 | ≈ 53.60 |
| 10 | not rated | not rated | not rated | not rated | ≈ 62.64 | 66.40 | 70.91 | 77.02 |
| 12 | not rated | not rated | not rated | not rated | not rated | 85.44 | 91.58 | 99.24 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 15.35 | ≈ 13.72 | ≈ 13.74 | ≈ 13.66 |
| 8 | not rated | not rated | not rated | not rated | ≈ 24.76 | ≈ 35.13 | ≈ 38.82 | ≈ 43.69 |
| 10 | not rated | not rated | not rated | not rated | ≈ 34.37 | 53.29 | 57.46 | 62.58 |
| 12 | not rated | not rated | not rated | not rated | not rated | 68.73 | 74.06 | 80.41 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 66.396 | 20.83 | 93.8 |
| Low speed (Y) | 53.293 | 16.72 | 63.6 |
| A | 4028 mm |
|---|---|
| B | 1720 mm |
| C | 455 mm |
| F | 1645 mm |
| G | 483 mm |
| E1 | 3635 mm |
| E2 | 1218 mm |
| E3 | 1200 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 4028 mm |
|---|---|
| Width | 1720 mm |
| Height | 483 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.