Skip to Content

Brine cooler ED-G-450AG4-A21 C

Brine cooler ED-G-450AG4-A21 C
Illustrative photo

Producer: Karyer · Line: ED-G (General)

Product code: ED-G-450AG4-A21 C

Cooling capacity i
70.94 kW
Air flow
24,556 m³/h
Fin spacing
4.2 mm
Air throw
19 m
Fans
4 × ⌀500 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 24,556 m³/h
Air throw 19 m
External surface 365.2 m²
Inner volume 79.0 dm³
Fin spacing 4.2 mm
Fin materialAluminium
Net weight 325 kg
Fans
Quantity 4
Diameter 500 mm
Speed 1,300 rpm
Power 2,720 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 62.0 dB(A)
Sound power 84.7 dB(A)
Energy class E
Connections
Inlet 2"
Outlet 2"
Defrost
ED-G-450AG4-A21 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · Single phase
70.944 kW Sensible capacity 50.842 kW Fluid flow 22.25 m³/h Pressure drop 78.0 kPa above the recommended pressure drop

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

Single phase

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 18.65 16.88 ≈ 16.95 ≈ 16.94
8 not rated not rated not rated not rated 30.35 ≈ 28.40 ≈ 51.46 ≈ 59.33
10 not rated not rated not rated not rated ≈ 42.49 70.94 77.98 86.11
12 not rated not rated not rated not rated not rated 92.65 101.31 111.06

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 70.944 22.25 78.0

Dimensions

Dimension drawing of ED-G-450AG4-A21 C
Dimension drawing
Dimensions as drawn
A 4428 mm
B 1350 mm
C 405 mm
F 1135 mm
G 506 mm
E1 4035 mm
E2 1018 mm
E3 1000 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 4428 mm
Width 1350 mm
Height 506 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.