- Catalogue
- Condensers
- KA/KB (General)
KA/KB (General)
- Refrigerants
- R134a, R22, R290, R32, R404A, R407A, R407B, R407C, R407F, R410A, R448A, R449A, R450a, R452a, R454A, R454C, R455A, R507A, R513a
- Capacity
- 14.80–1425.75 kW
- Fans
- ⌀500, ⌀630, ⌀800, ⌀910 mm
- Max. working pressure
- 27 bar
Model nomenclature
How to read the model codes of this series, with an example.
-
A
Series KA/KB = KA = vertical, KB = horizontal industrial condenser.
-
B
Fin type (optional "t") — = absent: standard corrugated finst = t: louvered fins (high-efficiency fin surface)
-
C
Fan rows (optional "Nx") — Catalogue: "Fan Row no." (number before x/X). — = absent: 1 fan row2x = 2 fan rows
-
D
Number of fans per row — Digit 1-9; total fans = fan rows x this digit.
-
E
Fan diameter — Two digits = diameter / 10 (91 = Ø910). 50 = Ø500 mm63 = Ø630 mm80 = Ø800 mm91 = Ø910 mm
-
G
Coil tube rows (2nd dimensional letter) A = 2 tube rowsB = 3 tube rowsC = 4 tube rowsD = 5 tube rows
-
H
Fin spacing — Catalogue fin-spacing code. 1 = 2.1 mm5 = 2.5 mm
-
I
Generation code — Catalogue: "Generation Code". B = generation B
-
J
Fan data (fan motor code) — Catalogue: "Fan Data". Two digits select the fan motor (supply, poles); the meaning is series-specific. 01 = fan motor code; supply/poles vary with diameter03 = three-phase 400 V 50 Hz, 12-pole AC fan (in this series)04 = fan motor code; supply/poles vary with diameter06 = three-phase 400 V 50 Hz, 6-pole AC fan (in this series)08 = three-phase 400 V 50 Hz, 4-pole AC fan (in this series)09 = single-phase 230 V 50 Hz, 4-pole AC fan (in this series)10 = three-phase 400 V 50 Hz, 4-pole AC fan (in this series)19 = three-phase 400 V 50 Hz, 4-pole AC fan (in this series)
| Model | Heat rejection [kW] i Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 % | Fans | Air flow [m³/h] | Variants |
|---|---|---|---|---|
| KA/KB-t-2x250EB1-B09 C | 100.12 kW | 4 × ⌀500 | 27,331 |
Variants (1) |
| KA/KB-t-480EA5-B03 C | 100.33 kW | 4 × ⌀800 | 38,034 |
Variants (1) |
| KA/KB-2x250CC1-B09 C | 100.51 kW | 4 × ⌀500 | 26,969 |
Variants (1) |
| KA/KB-450BC5-B01I C | 100.51 kW | 4 × ⌀500 | 27,831 |
Variants (1) |
| KA/KB-550AB1-B01I C | 100.53 kW | 5 × ⌀500 | 33,674 |
Variants (1) |
| KA/KB-t-363EB1-B01 C | 100.55 kW | 3 × ⌀630 | 25,541 |
Variants (1) |
| KA/KB-t-380EA5-B01 C | 100.64 kW | 3 × ⌀800 | 58,105 |
Variants (1) |
| KA/KB-550AB1-B10 C | 100.65 kW | 5 × ⌀500 | 33,848 |
Variants (1) |
| KA/KB-2x163AD5-B08 C | 100.68 kW | 2 × ⌀630 | 27,259 |
Variants (1) |
| KA/KB-180JD1-B01 C | 100.96 kW | 1 × ⌀800 | 21,467 |
Variants (1) |
| KA/KB-550BB5-B09 C | 101.13 kW | 5 × ⌀500 | 35,557 |
Variants (1) |
| KA/KB-263FB1-B19 C | 101.14 kW | 2 × ⌀630 | 25,722 |
Variants (1) |
| KA/KB-t-450EB1-B09 C | 101.14 kW | 4 × ⌀500 | 27,468 |
Variants (1) |
| KA/KB-t-263HB5-B19 C | 101.22 kW | 2 × ⌀630 | 25,658 |
Variants (1) |
| KA/KB-2x163GB5-B08 C | 101.31 kW | 2 × ⌀630 | 33,971 |
Variants (1) |
| KA/KB-2x180AB1-B01I C | 101.34 kW | 2 × ⌀800 | 34,755 |
Variants (1) |
| KA/KB-2x163FB1-B19 C | 101.37 kW | 2 × ⌀630 | 25,722 |
Variants (1) |
| KA/KB-191GD1-B04 C | 101.38 kW | 1 × ⌀910 | 25,395 |
Variants (1) |
| KA/KB-t-2x350EA5-B09 C | 101.43 kW | 6 × ⌀500 | 43,960 |
Variants (1) |
| KA/KB-2x250AD1-B01I C | 101.49 kW | 4 × ⌀500 | 23,755 |
Variants (1) |
| KA/KB-450CC1-B09 C | 101.51 kW | 4 × ⌀500 | 27,144 |
Variants (1) |
| KA/KB-550CC1-B04 C | 101.71 kW | 5 × ⌀500 | 23,731 |
Variants (1) |
| KA/KB-t-550EB1-B04 C | 101.74 kW | 5 × ⌀500 | 24,064 |
Variants (1) |
| KA/KB-191GD1-B04I C | 101.74 kW | 1 × ⌀910 | 25,511 |
Variants (1) |
| KA/KB-191CD1-B04 C | 101.78 kW | 1 × ⌀910 | 25,068 |
Variants (1) |
| KA/KB-263GB5-B08 C | 101.87 kW | 2 × ⌀630 | 34,011 |
Variants (1) |
| KA/KB-550BC1-B04 C | 101.88 kW | 5 × ⌀500 | 23,323 |
Variants (1) |
| KA/KB-2x350BB5-B04 C | 101.90 kW | 6 × ⌀500 | 30,063 |
Variants (1) |
| KA/KB-2x250CC1-B10 C | 101.92 kW | 4 × ⌀500 | 27,684 |
Variants (1) |
| KA/KB-t-2x163HB5-B19 C | 101.94 kW | 2 × ⌀630 | 25,632 |
Variants (1) |
| KA/KB-450AD1-B01I C | 101.96 kW | 4 × ⌀500 | 23,755 |
Variants (1) |
| KA/KB-t-463EA1-B01 C | 101.98 kW | 4 × ⌀630 | 36,366 |
Variants (1) |
| KA/KB-363AB5-B19 C | 102.12 kW | 3 × ⌀630 | 35,889 |
Variants (1) |
| KA/KB-191CD1-B04I C | 102.13 kW | 1 × ⌀910 | 25,178 |
Variants (1) |
| KA/KB-2x250CC1-B01I C | 102.17 kW | 4 × ⌀500 | 27,560 |
Variants (1) |
| KA/KB-550CD5-B04 C | 102.26 kW | 5 × ⌀500 | 23,194 |
Variants (1) |
| KA/KB-t-2x250EB1-B10 C | 102.31 kW | 4 × ⌀500 | 28,043 |
Variants (1) |
| KA/KB-550BB5-B10 C | 102.33 kW | 5 × ⌀500 | 36,590 |
Variants (1) |
| KA/KB-t-650EA5-B09 C | 102.33 kW | 6 × ⌀500 | 44,122 |
Variants (1) |
| KA/KB-280AB1-B01I C | 102.33 kW | 2 × ⌀800 | 34,755 |
Variants (1) |
| KA/KB-t-2x180EB1-B01I C | 102.49 kW | 2 × ⌀800 | 31,397 |
Variants (1) |
| KA/KB-263AD5-B08 C | 102.68 kW | 2 × ⌀630 | 27,259 |
Variants (1) |
| KA/KB-550BB5-B01I C | 102.69 kW | 5 × ⌀500 | 36,424 |
Variants (1) |
| KA/KB-450CC1-B10 C | 102.88 kW | 4 × ⌀500 | 27,841 |
Variants (1) |
| KA/KB-363BC1-B06I C | 102.90 kW | 3 × ⌀630 | 24,899 |
Variants (1) |
| KA/KB-450CC1-B01I C | 103.14 kW | 4 × ⌀500 | 27,720 |
Variants (1) |
| KA/KB-2x350AC5-B04 C | 103.18 kW | 6 × ⌀500 | 26,401 |
Variants (1) |
| KA/KB-t-450EB1-B10 C | 103.39 kW | 4 × ⌀500 | 28,196 |
Variants (1) |
| KA/KB-t-463EA5-B19 C | 103.73 kW | 4 × ⌀630 | 49,011 |
Variants (1) |
| KA/KB-t-280EB1-B01I C | 103.73 kW | 2 × ⌀800 | 31,603 |
Variants (1) |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
Downloads
- KA/KB-t-2x250EB1-B09 C — product datasheet (PDF)
- KA/KB-t-480EA5-B03 C — product datasheet (PDF)
- KA/KB-2x250CC1-B09 C — product datasheet (PDF)
- KA/KB-450BC5-B01I C — product datasheet (PDF)
- KA/KB-550AB1-B01I C — product datasheet (PDF)
- KA/KB-t-363EB1-B01 C — product datasheet (PDF)
- KA/KB-t-380EA5-B01 C — product datasheet (PDF)
- KA/KB-550AB1-B10 C — product datasheet (PDF)
- KA/KB-2x163AD5-B08 C — product datasheet (PDF)
- KA/KB-180JD1-B01 C — product datasheet (PDF)
- KA/KB-550BB5-B09 C — product datasheet (PDF)
- KA/KB-263FB1-B19 C — product datasheet (PDF)
- KA/KB-t-450EB1-B09 C — product datasheet (PDF)
- KA/KB-t-263HB5-B19 C — product datasheet (PDF)
- KA/KB-2x163GB5-B08 C — product datasheet (PDF)
- KA/KB-2x180AB1-B01I C — product datasheet (PDF)
- KA/KB-2x163FB1-B19 C — product datasheet (PDF)
- KA/KB-191GD1-B04 C — product datasheet (PDF)
- KA/KB-t-2x350EA5-B09 C — product datasheet (PDF)
- KA/KB-2x250AD1-B01I C — product datasheet (PDF)
- KA/KB-450CC1-B09 C — product datasheet (PDF)
- KA/KB-550CC1-B04 C — product datasheet (PDF)
- KA/KB-t-550EB1-B04 C — product datasheet (PDF)
- KA/KB-191GD1-B04I C — product datasheet (PDF)
- KA/KB-191CD1-B04 C — product datasheet (PDF)
- KA/KB-263GB5-B08 C — product datasheet (PDF)
- KA/KB-550BC1-B04 C — product datasheet (PDF)
- KA/KB-2x350BB5-B04 C — product datasheet (PDF)
- KA/KB-2x250CC1-B10 C — product datasheet (PDF)
- KA/KB-t-2x163HB5-B19 C — product datasheet (PDF)
- KA/KB-450AD1-B01I C — product datasheet (PDF)
- KA/KB-t-463EA1-B01 C — product datasheet (PDF)
- KA/KB-363AB5-B19 C — product datasheet (PDF)
- KA/KB-191CD1-B04I C — product datasheet (PDF)
- KA/KB-2x250CC1-B01I C — product datasheet (PDF)
- KA/KB-550CD5-B04 C — product datasheet (PDF)
- KA/KB-t-2x250EB1-B10 C — product datasheet (PDF)
- KA/KB-550BB5-B10 C — product datasheet (PDF)
- KA/KB-t-650EA5-B09 C — product datasheet (PDF)
- KA/KB-280AB1-B01I C — product datasheet (PDF)
- KA/KB-t-2x180EB1-B01I C — product datasheet (PDF)
- KA/KB-263AD5-B08 C — product datasheet (PDF)
- KA/KB-550BB5-B01I C — product datasheet (PDF)
- KA/KB-450CC1-B10 C — product datasheet (PDF)
- KA/KB-363BC1-B06I C — product datasheet (PDF)
- KA/KB-450CC1-B01I C — product datasheet (PDF)
- KA/KB-2x350AC5-B04 C — product datasheet (PDF)
- KA/KB-t-450EB1-B10 C — product datasheet (PDF)
- KA/KB-t-463EA5-B19 C — product datasheet (PDF)
- KA/KB-t-280EB1-B01I C — product datasheet (PDF)
Ask about product
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.