Skip to Content

Condenser KC-2x280BB5-B01T C

Condenser KC-2x280BB5-B01T C
Illustrative photo

Producer: Karyer · Line: KC (Dry)

Product code: KC-2x280BB5-B01T C

Heat rejection i
273.36 kW
Air flow
91,727 m³/h
Fin spacing
2.5 mm
Fans
4 × ⌀800 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 91,727 m³/h
External surface 601.3 m²
Inner volume 84.5 dm³
Fin spacing 2.5 mm
Fin materialAluminium
Net weight 1,172 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.5 dB(A)
Energy class D
Connections
Inlet Ø42
Outlet Ø35
Defrost
KC-2x280BB5-B01T C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · High speed (Δ)
276.692 kW Refrigerant flow 6,479 kg/h
Heat rejection · Low speed (Y)
224.283 kW Refrigerant flow 5,252 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
High speed (Δ) 276.69 277.88 279.60 282.12 285.81 291.51
Low speed (Y) 224.28 224.82 225.82 227.47 230.07 234.23

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
High speed (Δ) 276.692
Low speed (Y) 224.283

Dimensions

Dimension drawing of KC-2x280BB5-B01T C
Dimension drawing
Dimensions as drawn
A 2778 mm
B 2400 mm
C 2650 mm
F 2330 mm
G 2900 mm
E1 1150 mm
D IN Ø42
D OUT Ø35
Overall [mm]
Length 2900 mm
Width 2400 mm
Height 2778 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.