KC-291CD1-B04 C
274.56 kW
Defrost: None
Product code: KC-463AD5-B08 C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 65,138 m³/h |
|---|---|
| External surface | 746.4 m² |
| Inner volume | 94.5 dm³ |
| Fin spacing | 2.5 mm |
| Fin material | Aluminium |
| Net weight | 459 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 7,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 98.0 dB(A) |
| Energy class | D |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø42 |
| KC-463AD5-B08 C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| High speed (Δ) | 277.68 | 277.36 | 277.27 | 277.57 | 278.44 | 280.19 |
| Low speed (Y) | 226.40 | 225.70 | 225.23 | 225.13 | 225.51 | 226.60 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| High speed (Δ) | 277.679 |
| Low speed (Y) | 226.396 |
| A | 1560 mm |
|---|---|
| B | 1150 mm |
| C | 4000 mm |
| F | 1060 mm |
| E1 | 930 mm |
| E2 | 900 mm |
| D IN | Ø54 |
| D OUT | Ø42 |
| Length | 4000 mm |
|---|---|
| Width | 1150 mm |
| Height | 1560 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.