- Catalogue
- Condensers
- KC-MF (Modular V-type with chassis)
KC-MF (Modular V-type with chassis)
- Refrigerants
- R134a, R22, R290, R32, R404A, R407A, R407B, R407C, R407F, R410A, R448A, R449A, R450a, R452a, R454A, R454C, R455A, R507A, R513a
- Capacity
- 84.60–1082.43 kW
- Fans
- ⌀500, ⌀800 mm
- Max. working pressure
- 27 bar
Model nomenclature
How to read the model codes of this series, with an example.
-
A
Series KC-M = KC-MF = modular V-type condenser with bottom chassis (catalogue "KCM"); "KC-M" = single-module form written without Nx.KC-MF = KC-MF = modular V-type condenser with bottom chassis (catalogue "KCM"); "KC-M" = single-module form written without Nx.
-
B
Fin type (optional "t") — = absent: standard corrugated finst = t: louvered fins (high-efficiency fin surface)
-
C
Fan rows (optional "Nx") — Catalogue: "Fan Row no." (number before x/X). For KC-MF it counts the modules; total fans = modules x fans per module. — = absent: 1 fan row2x = 2 fan rows3x = 3 fan rows (modules)4x = 4 fan rows (modules)5x = 5 fan rows (modules)6x = 6 fan rows (modules)
-
D
Number of fans per row — Digit 1-9; total fans = fan rows x this digit.
-
E
Fan diameter — Two digits = diameter / 10 (91 = Ø910). 50 = Ø500 mm80 = Ø800 mm
-
G
Coil tube rows (2nd dimensional letter) B = 3 tube rowsC = 4 tube rowsD = 5 tube rows
-
H
Fin spacing — Catalogue fin-spacing code. 1 = 2.1 mm5 = 2.5 mm
-
I
Generation code — Catalogue: "Generation Code". B = generation B
-
J
Fan data (fan motor code) — Catalogue: "Fan Data". Two digits select the fan motor (supply, poles); the meaning is series-specific. 01 = three-phase 400 V 50 Hz, 6-pole AC fan (in this series)09 = single-phase 230 V 50 Hz, 4-pole AC fan (in this series)
| Model | Heat rejection [kW] i Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 % | Fans | Air flow [m³/h] | Variants |
|---|---|---|---|---|
| KC-M-350GB5-B09 C | 84.60 kW | 3 × ⌀500 | 23,917 |
Variants (1)
|
| KC-MF-350GB5-B09 C | 84.60 kW | 3 × ⌀500 | 23,917 |
Variants (1) |
| KC-M-350GB1-B09 C | 93.57 kW | 3 × ⌀500 | 23,817 |
Variants (1)
|
| KC-MF-350GB1-B09 C | 93.57 kW | 3 × ⌀500 | 23,817 |
Variants (1) |
| KC-M-350GC5-B09 C | 100.17 kW | 3 × ⌀500 | 23,626 |
Variants (1)
|
| KC-MF-350GC5-B09 C | 100.17 kW | 3 × ⌀500 | 23,626 |
Variants (1) |
| KC-M-350GC1-B09 C | 109.32 kW | 3 × ⌀500 | 23,498 |
Variants (1)
|
| KC-MF-350GC1-B09 C | 109.32 kW | 3 × ⌀500 | 23,498 |
Variants (1) |
| KC-M-350GD1-B09 C | 109.79 kW | 3 × ⌀500 | 23,113 |
Variants (1)
|
| KC-MF-350GD1-B09 C | 109.79 kW | 3 × ⌀500 | 23,113 |
Variants (1) |
| KC-M-350GD5-B09 C | 110.77 kW | 3 × ⌀500 | 23,337 |
Variants (1)
|
| KC-MF-350GD5-B09 C | 110.77 kW | 3 × ⌀500 | 23,337 |
Variants (1) |
| KC-M-280GB5-B01 C | 124.32 kW | 2 × ⌀800 | 44,347 |
Variants (1)
|
| KC-MF-280GB5-B01 C | 124.32 kW | 2 × ⌀800 | 44,347 |
Variants (1) |
| KC-M-280GB1-B01 C | 138.79 kW | 2 × ⌀800 | 43,777 |
Variants (1)
|
| KC-MF-280GB1-B01 C | 138.79 kW | 2 × ⌀800 | 43,777 |
Variants (1) |
| KC-M-280GC5-B01 C | 149.40 kW | 2 × ⌀800 | 42,739 |
Variants (1)
|
| KC-MF-280GC5-B01 C | 149.40 kW | 2 × ⌀800 | 42,739 |
Variants (1) |
| KC-M-280GC1-B01 C | 163.53 kW | 2 × ⌀800 | 42,014 |
Variants (1)
|
| KC-MF-280GC1-B01 C | 163.53 kW | 2 × ⌀800 | 42,014 |
Variants (1) |
| KC-M-280GD5-B01 C | 166.70 kW | 2 × ⌀800 | 41,156 |
Variants (1)
|
| KC-MF-280GD5-B01 C | 166.70 kW | 2 × ⌀800 | 41,156 |
Variants (1) |
| KC-M-280GD1-B01 C | 180.41 kW | 2 × ⌀800 | 40,319 |
Variants (1)
|
| KC-MF-280GD1-B01 C | 180.41 kW | 2 × ⌀800 | 40,319 |
Variants (1) |
| KC-MF-2x350GB1-B09 C | 187.14 kW | 6 × ⌀500 | 47,633 |
Variants (1) |
| KC-MF-2x350GC1-B09 C | 218.64 kW | 6 × ⌀500 | 46,996 |
Variants (1) |
| KC-MF-2x350GD1-B09 C | 219.57 kW | 6 × ⌀500 | 46,227 |
Variants (1) |
| KC-MF-2x280GB1-B01 C | 277.57 kW | 4 × ⌀800 | 87,553 |
Variants (1) |
| KC-MF-3x350GB1-B09 C | 280.71 kW | 9 × ⌀500 | 71,450 |
Variants (1) |
| KC-MF-2x280GC1-B01 C | 327.05 kW | 4 × ⌀800 | 84,028 |
Variants (1) |
| KC-MF-3x350GC1-B09 C | 327.96 kW | 9 × ⌀500 | 70,494 |
Variants (1) |
| KC-MF-3x350GD1-B09 C | 329.35 kW | 9 × ⌀500 | 69,340 |
Variants (1) |
| KC-MF-2x280GD1-B01 C | 360.81 kW | 4 × ⌀800 | 80,639 |
Variants (1) |
| KC-MF-4x350GB1-B09 C | 374.29 kW | 12 × ⌀500 | 95,267 |
Variants (1) |
| KC-MF-3x280GB1-B01 C | 416.36 kW | 6 × ⌀800 | 131,330 |
Variants (1) |
| KC-MF-4x350GC1-B09 C | 437.28 kW | 12 × ⌀500 | 93,992 |
Variants (1) |
| KC-MF-4x350GD1-B09 C | 439.14 kW | 12 × ⌀500 | 92,454 |
Variants (1) |
| KC-MF-5x350GB1-B09 C | 467.86 kW | 15 × ⌀500 | 119,083 |
Variants (1) |
| KC-MF-3x280GC1-B01 C | 490.58 kW | 6 × ⌀800 | 126,041 |
Variants (1) |
| KC-MF-3x280GD1-B01 C | 541.22 kW | 6 × ⌀800 | 120,958 |
Variants (1) |
| KC-MF-5x350GC1-B09 C | 546.60 kW | 15 × ⌀500 | 117,490 |
Variants (1) |
| KC-MF-5x350GD1-B09 C | 548.93 kW | 15 × ⌀500 | 115,567 |
Variants (1) |
| KC-MF-4x280GB1-B01 C | 555.15 kW | 8 × ⌀800 | 175,107 |
Variants (1) |
| KC-MF-6x350GB1-B09 C | 561.43 kW | 18 × ⌀500 | 142,900 |
Variants (1) |
| KC-MF-4x280GC1-B01 C | 654.11 kW | 8 × ⌀800 | 168,055 |
Variants (1) |
| KC-MF-6x350GC1-B09 C | 655.92 kW | 18 × ⌀500 | 140,988 |
Variants (1) |
| KC-MF-6x350GD1-B09 C | 658.71 kW | 18 × ⌀500 | 138,681 |
Variants (1) |
| KC-MF-5x280GB1-B01 C | 693.94 kW | 10 × ⌀800 | 218,883 |
Variants (1) |
| KC-MF-4x280GD1-B01 C | 721.62 kW | 8 × ⌀800 | 161,277 |
Variants (1) |
| KC-MF-5x280GC1-B01 C | 817.63 kW | 10 × ⌀800 | 210,069 |
Variants (1) |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
Downloads
- KC-M-350GB5-B09 C — product datasheet (PDF)
- KC-MF-350GB5-B09 C — product datasheet (PDF)
- KC-M-350GB1-B09 C — product datasheet (PDF)
- KC-MF-350GB1-B09 C — product datasheet (PDF)
- KC-M-350GC5-B09 C — product datasheet (PDF)
- KC-MF-350GC5-B09 C — product datasheet (PDF)
- KC-M-350GC1-B09 C — product datasheet (PDF)
- KC-MF-350GC1-B09 C — product datasheet (PDF)
- KC-M-350GD1-B09 C — product datasheet (PDF)
- KC-MF-350GD1-B09 C — product datasheet (PDF)
- KC-M-350GD5-B09 C — product datasheet (PDF)
- KC-MF-350GD5-B09 C — product datasheet (PDF)
- KC-M-280GB5-B01 C — product datasheet (PDF)
- KC-MF-280GB5-B01 C — product datasheet (PDF)
- KC-M-280GB1-B01 C — product datasheet (PDF)
- KC-MF-280GB1-B01 C — product datasheet (PDF)
- KC-M-280GC5-B01 C — product datasheet (PDF)
- KC-MF-280GC5-B01 C — product datasheet (PDF)
- KC-M-280GC1-B01 C — product datasheet (PDF)
- KC-MF-280GC1-B01 C — product datasheet (PDF)
- KC-M-280GD5-B01 C — product datasheet (PDF)
- KC-MF-280GD5-B01 C — product datasheet (PDF)
- KC-M-280GD1-B01 C — product datasheet (PDF)
- KC-MF-280GD1-B01 C — product datasheet (PDF)
- KC-MF-2x350GB1-B09 C — product datasheet (PDF)
- KC-MF-2x350GC1-B09 C — product datasheet (PDF)
- KC-MF-2x350GD1-B09 C — product datasheet (PDF)
- KC-MF-2x280GB1-B01 C — product datasheet (PDF)
- KC-MF-3x350GB1-B09 C — product datasheet (PDF)
- KC-MF-2x280GC1-B01 C — product datasheet (PDF)
- KC-MF-3x350GC1-B09 C — product datasheet (PDF)
- KC-MF-3x350GD1-B09 C — product datasheet (PDF)
- KC-MF-2x280GD1-B01 C — product datasheet (PDF)
- KC-MF-4x350GB1-B09 C — product datasheet (PDF)
- KC-MF-3x280GB1-B01 C — product datasheet (PDF)
- KC-MF-4x350GC1-B09 C — product datasheet (PDF)
- KC-MF-4x350GD1-B09 C — product datasheet (PDF)
- KC-MF-5x350GB1-B09 C — product datasheet (PDF)
- KC-MF-3x280GC1-B01 C — product datasheet (PDF)
- KC-MF-3x280GD1-B01 C — product datasheet (PDF)
- KC-MF-5x350GC1-B09 C — product datasheet (PDF)
- KC-MF-5x350GD1-B09 C — product datasheet (PDF)
- KC-MF-4x280GB1-B01 C — product datasheet (PDF)
- KC-MF-6x350GB1-B09 C — product datasheet (PDF)
- KC-MF-4x280GC1-B01 C — product datasheet (PDF)
- KC-MF-6x350GC1-B09 C — product datasheet (PDF)
- KC-MF-6x350GD1-B09 C — product datasheet (PDF)
- KC-MF-5x280GB1-B01 C — product datasheet (PDF)
- KC-MF-4x280GD1-B01 C — product datasheet (PDF)
- KC-MF-5x280GC1-B01 C — product datasheet (PDF)
Ask about product
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.