Skip to Content

Condenser KC-MF-5x350GB1-B09 C

Condenser KC-MF-5x350GB1-B09 C
Illustrative photo

Producer: Karyer · Line: KC-MF (Modular V-type with chassis)

Product code: KC-MF-5x350GB1-B09 C

Heat rejection i
467.86 kW
Air flow
119,083 m³/h
Fin spacing
2.1 mm
Fans
15 × ⌀500 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 119,083 m³/h
External surface 1,458.7 m²
Inner volume 181.1 dm³
Fin spacing 2.1 mm
Fin materialAluminium
Net weight 2,394 kg
Fans
Quantity 15
Diameter 500 mm
Speed 1,330 rpm
Power 10,650 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.5 dB(A)
Energy class D
Connections
Inlet Ø28
Outlet Ø22
Defrost
KC-MF-5x350GB1-B09 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
473.415 kW Refrigerant flow 11,086 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 473.42 472.49 472.43 473.54 476.31 481.75

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 473.415

Dimensions

Dimension drawing of KC-MF-5x350GB1-B09 C
Dimension drawing
Dimensions as drawn
A 2260 mm
B 2060 mm
C 5200 mm
E 900 mm
D IN Ø28
D OUT Ø22
Overall [mm]
Length 2060 mm
Width 5200 mm
Height 2260 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.