KC-MF-5x350GD1-B09 C
548.93 kW
Defrost: None
Product code: KC-MF-5x350GC1-B09 C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 117,490 m³/h |
|---|---|
| External surface | 1,945.8 m² |
| Inner volume | 229.7 dm³ |
| Fin spacing | 2.1 mm |
| Fin material | Aluminium |
| Net weight | 2,542 kg |
| Quantity | 15 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 10,650 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.5 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø22 |
| KC-MF-5x350GC1-B09 C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| Single phase | 552.75 | 549.39 | 546.46 | 544.14 | 542.68 | 542.32 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| Single phase | 552.752 |
| A | 2260 mm |
|---|---|
| B | 2060 mm |
| C | 5200 mm |
| E | 900 mm |
| D IN | Ø28 |
| D OUT | Ø22 |
| Length | 2060 mm |
|---|---|
| Width | 5200 mm |
| Height | 2260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.