Skip to Content

Condenser KC-MF-6x350GC1-B09 C

Condenser KC-MF-6x350GC1-B09 C
Illustrative photo

Producer: Karyer · Line: KC-MF (Modular V-type with chassis)

Product code: KC-MF-6x350GC1-B09 C

Heat rejection i
655.92 kW
Air flow
140,988 m³/h
Fin spacing
2.1 mm
Fans
18 × ⌀500 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 140,988 m³/h
External surface 2,335.0 m²
Inner volume 282.1 dm³
Fin spacing 2.1 mm
Fin materialAluminium
Net weight 3,050 kg
Fans
Quantity 18
Diameter 500 mm
Speed 1,330 rpm
Power 12,780 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet Ø28
Outlet Ø22
Defrost
KC-MF-6x350GC1-B09 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
663.303 kW Refrigerant flow 15,533 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 663.30 659.27 655.75 652.97 651.21 650.79

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 663.303

Dimensions

Dimension drawing of KC-MF-6x350GC1-B09 C
Dimension drawing
Dimensions as drawn
A 2260 mm
B 2060 mm
C 6240 mm
E 900 mm
D IN Ø28
D OUT Ø22
Overall [mm]
Length 2060 mm
Width 6240 mm
Height 2260 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.