Skip to Content

Condenser KC-WF-2x280AA5-B01T C

Condenser KC-WF-2x280AA5-B01T C
Illustrative photo

Producer: Karyer · Line: KC-WF (W-type)

Product code: KC-WF-2x280AA5-B01T C

Heat rejection i
261.88 kW
Air flow
95,499 m³/h
Fin spacing
2.5 mm
Fans
4 × ⌀800 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 95,499 m³/h
External surface 635.1 m²
Inner volume 87.5 dm³
Fin spacing 2.5 mm
Fin materialAluminium
Net weight 1,721 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 87.0 dB(A)
Energy class D
Connections
Inlet Ø28
Outlet Ø28
Defrost
KC-WF-2x280AA5-B01T C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · High speed (Δ)
265.057 kW Refrigerant flow 6,207 kg/h
Heat rejection · Low speed (Y)
220.134 kW Refrigerant flow 5,155 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
High speed (Δ) 265.06 266.51 268.45 271.13 274.96 281.02
Low speed (Y) 220.13 220.84 221.99 223.78 226.52 230.86

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
High speed (Δ) 265.057
Low speed (Y) 220.134

Dimensions

Dimension drawing of KC-WF-2x280AA5-B01T C
Dimension drawing
Dimensions as drawn
A 2670 mm
B 2400 mm
C 2900 mm
E 1000 mm
D IN Ø28
D OUT Ø28
Overall [mm]
Length 2900 mm
Width 2400 mm
Height 2670 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.