KC-WF-2x291AB1-C04C C
382.72 kW
Defrost: None
Product code: KC-WF-2x280BD5-B01T C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 88,377 m³/h |
|---|---|
| External surface | 1,092.3 m² |
| Inner volume | 136.1 dm³ |
| Fin spacing | 2.5 mm |
| Fin material | Aluminium |
| Net weight | 1,836 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø28 |
| KC-WF-2x280BD5-B01T C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| High speed (Δ) | 385.39 | 384.99 | 384.80 | 385.03 | 385.95 | 387.85 |
| Low speed (Y) | 295.16 | 294.11 | 293.34 | 292.99 | 293.21 | 294.23 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| High speed (Δ) | 385.388 |
| Low speed (Y) | 295.163 |
| A | 2670 mm |
|---|---|
| B | 2400 mm |
| C | 2700 mm |
| E | 1000 mm |
| D IN | Ø35 |
| D OUT | Ø28 |
| Length | 2700 mm |
|---|---|
| Width | 2400 mm |
| Height | 2670 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.