KC-WF-2x391AB5-C04C C
532.95 kW
Defrost: None
Product code: KC-WF-2x580BA5-B01T C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 237,587 m³/h |
|---|---|
| External surface | 1,092.3 m² |
| Inner volume | 146.3 dm³ |
| Fin spacing | 2.5 mm |
| Fin material | Aluminium |
| Net weight | 3,254 kg |
| Quantity | 10 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 18,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø35 |
| KC-WF-2x580BA5-B01T C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| High speed (Δ) | 539.08 | 541.75 | 546.32 | 553.47 | 564.47 | 582.21 |
| Low speed (Y) | 446.07 | 447.80 | 451.06 | 456.38 | 464.75 | 478.44 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| High speed (Δ) | 539.077 |
| Low speed (Y) | 446.067 |
| A | 2670 mm |
|---|---|
| B | 2400 mm |
| C | 6000 mm |
| E | 1000 mm |
| D IN | Ø42 |
| D OUT | Ø35 |
| Length | 6000 mm |
|---|---|
| Width | 2400 mm |
| Height | 2670 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.