BC/BD-2X150CC1-B09 C
34.59 kW
Defrost: None
Product code: BC/BD-163BC1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 11,257 m³/h |
|---|---|
| External surface | 93.1 m² |
| Inner volume | 12.4 dm³ |
| Fin material | Aluminium |
| Net weight | 132 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 1,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-163BC1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 19.72 | not rated | not rated | not rated | not rated | not rated |
| 40 | 34.56 | 19.84 | not rated | not rated | not rated | not rated |
| 45 | 49.01 | 34.58 | 19.95 | not rated | not rated | not rated |
| 50 | 63.33 | 48.94 | 34.60 | 20.05 | not rated | not rated |
| 55 | 77.59 | 63.17 | 48.88 | 34.63 | 20.15 | not rated |
| 60 | 91.83 | 77.36 | 63.05 | 48.85 | 34.67 | 20.26 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 16.64 | not rated | not rated | not rated | not rated | not rated |
| 40 | 29.00 | 16.75 | not rated | not rated | not rated | not rated |
| 45 | 41.00 | 29.01 | 16.84 | not rated | not rated | not rated |
| 50 | 52.88 | 40.93 | 29.03 | 16.93 | not rated | not rated |
| 55 | 64.71 | 52.74 | 40.88 | 29.05 | 17.01 | not rated |
| 60 | 76.50 | 64.50 | 52.63 | 40.85 | 29.09 | 17.10 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 34.558 | 6.00 | 39.1 |
| Low speed (Y) | 29.003 | 5.03 | 28.7 |
| A | 1250 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1000 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 1500 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 1250 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.