BC/BD-2X150CC1-B09 C
34.59 kW
Defrost: None
Product code: BC/BD-180KC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 9,726 m³/h |
|---|---|
| External surface | 153.3 m² |
| Inner volume | 19.8 dm³ |
| Fin material | Aluminium |
| Net weight | 225 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 32.0 dB(A) |
|---|---|
| Sound power | 64.0 dB(A) |
| Energy class | C |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| BC/BD-180KC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 20.44 | not rated | not rated | not rated | not rated | not rated |
| 40 | 34.63 | 20.50 | not rated | not rated | not rated | not rated |
| 45 | 48.42 | 34.58 | 20.54 | not rated | not rated | not rated |
| 50 | 62.07 | 48.26 | 34.53 | 20.59 | not rated | not rated |
| 55 | 75.67 | 61.83 | 48.14 | 34.50 | 20.65 | not rated |
| 60 | 89.23 | 75.35 | 61.64 | 48.06 | 34.51 | 20.71 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 16.00 | not rated | not rated | not rated | not rated | not rated |
| 40 | 26.92 | 16.04 | not rated | not rated | not rated | not rated |
| 45 | 37.49 | 26.87 | 16.08 | not rated | not rated | not rated |
| 50 | 47.95 | 37.36 | 26.82 | 16.12 | not rated | not rated |
| 55 | 58.35 | 47.75 | 37.26 | 26.80 | 16.17 | not rated |
| 60 | 68.73 | 58.09 | 47.59 | 37.19 | 26.81 | 16.24 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 34.634 | 6.01 | 34.5 |
| Low speed (Y) | 26.918 | 4.67 | 22.0 |
| A | 2100 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1850 mm |
| H | 1750 mm |
| I | 1180 mm |
| K | 2400 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 2400 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.