BC/BD-180KC5-B03 C
34.63 kW
Defrost: None
Product code: BC/BD-163CD5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 10,971 m³/h |
|---|---|
| External surface | 130.5 m² |
| Inner volume | 18.4 dm³ |
| Fin material | Aluminium |
| Net weight | 156 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 1,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| BC/BD-163CD5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 18.54 | not rated | not rated | not rated | not rated | not rated |
| 40 | 34.80 | 18.93 | not rated | not rated | not rated | not rated |
| 45 | 50.27 | 34.95 | 19.24 | not rated | not rated | not rated |
| 50 | 65.52 | 50.29 | 35.08 | 19.51 | not rated | not rated |
| 55 | 80.67 | 65.42 | 50.30 | 35.20 | 19.74 | not rated |
| 60 | 95.76 | 80.46 | 65.34 | 50.34 | 35.33 | 19.96 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 15.52 | not rated | not rated | not rated | not rated | not rated |
| 40 | 29.09 | 15.88 | not rated | not rated | not rated | not rated |
| 45 | 41.86 | 29.21 | 16.17 | not rated | not rated | not rated |
| 50 | 54.41 | 41.86 | 29.32 | 16.41 | not rated | not rated |
| 55 | 66.87 | 54.31 | 41.86 | 29.42 | 16.62 | not rated |
| 60 | 79.27 | 66.67 | 54.23 | 41.89 | 29.54 | 16.82 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 34.800 | 6.04 | 10.7 |
| Low speed (Y) | 29.092 | 5.05 | 7.7 |
| A | 1200 mm |
|---|---|
| B | 1200 mm |
| C | 1240 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1000 mm |
| H | 900 mm |
| I | 1190 mm |
| K | 1500 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 1500 mm |
|---|---|
| Width | 1240 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.