Skip to Content

Dry cooler BC/BD-163CB1-B19 C

Dry cooler BC/BD-163CB1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-163CB1-B19 C

Heat rejection i
29.79 kW
Air flow
11,631 m³/h
Fans
1 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 11,631 m³/h
External surface 92.7 m²
Inner volume 11.1 dm³
Fin materialAluminium
Net weight 141 kg
Fans
Quantity 1
Diameter 630 mm
Speed 1,330 rpm
Power 1,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class E
Connections
Inlet 1"
Outlet 1"
Defrost
BC/BD-163CB1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
29.790 kW Fluid flow 5.17 m³/h Pressure drop 23.9 kPa
Heat rejection · Low speed (Y)
25.544 kW Fluid flow 4.43 m³/h Pressure drop 18.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 15.70 not rated not rated not rated not rated not rated
40 29.79 16.00 not rated not rated not rated not rated
45 43.44 29.95 16.25 not rated not rated not rated
50 56.96 43.50 30.08 16.46 not rated not rated
55 70.42 56.93 43.55 30.20 16.65 not rated
60 83.85 70.31 56.91 43.60 30.32 16.83

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 13.51 not rated not rated not rated not rated not rated
40 25.54 13.78 not rated not rated not rated not rated
45 37.12 25.67 14.00 not rated not rated not rated
50 48.57 37.16 25.78 14.19 not rated not rated
55 59.96 48.53 37.20 25.88 14.36 not rated
60 71.32 59.85 48.50 37.24 25.99 14.52

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 29.790 5.17 23.9
Low speed (Y) 25.544 4.43 18.0

Dimensions

Dimension drawing of BC/BD-163CB1-B19 C
Dimension drawing
Dimensions as drawn
A 1200 mm
B 1200 mm
C 1240 mm
F 1050 mm
G 450 mm
E 1000 mm
H 900 mm
I 1190 mm
K 1500 mm
D IN 1"
D OUT 1"
Overall [mm]
Length 1500 mm
Width 1240 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.