Skip to Content

Dry cooler BC/BD-t-180GB1-B03 C

Dry cooler BC/BD-t-180GB1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-180GB1-B03 C

Heat rejection i
29.71 kW
Air flow
7,897 m³/h
Fans
1 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 7,897 m³/h
External surface 81.3 m²
Inner volume 10.1 dm³
Fin materialAluminium
Net weight 177 kg
Fans
Quantity 1
Diameter 800 mm
Speed 435 rpm
Power 300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 32.0 dB(A)
Sound power 64.0 dB(A)
Energy class C
Connections
Inlet 1 1/4"
Outlet 1 1/4"
Defrost
BC/BD-t-180GB1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
29.708 kW Fluid flow 5.15 m³/h Pressure drop 49.7 kPa
Heat rejection · Low speed (Y)
22.646 kW Fluid flow 3.93 m³/h Pressure drop 30.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 17.46 not rated not rated not rated not rated not rated
40 29.71 17.55 not rated not rated not rated not rated
45 41.58 29.71 17.63 not rated not rated not rated
50 53.33 41.52 29.73 17.71 not rated not rated
55 65.02 53.21 41.49 29.77 17.80 not rated
60 76.68 64.85 53.13 41.50 29.84 17.91

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 13.46 not rated not rated not rated not rated not rated
40 22.65 13.54 not rated not rated not rated not rated
45 31.52 22.67 13.61 not rated not rated not rated
50 40.28 31.50 22.70 13.69 not rated not rated
55 49.00 40.23 31.50 22.76 13.78 not rated
60 57.69 48.91 40.21 31.54 22.84 13.88

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 29.708 5.15 49.7
Low speed (Y) 22.646 3.93 30.7

Dimensions

Dimension drawing of BC/BD-t-180GB1-B03 C
Dimension drawing
Dimensions as drawn
A 1400 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 1150 mm
H 1050 mm
I 1180 mm
K 1700 mm
D IN 1 1/4"
D OUT 1 1/4"
Overall [mm]
Length 1700 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.