BC/BD-t-2X150AA5-B09 C
31.46 kW
Defrost: None
Product code: BC/BD-163CC5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 11,353 m³/h |
|---|---|
| External surface | 104.3 m² |
| Inner volume | 15.0 dm³ |
| Fin material | Aluminium |
| Net weight | 147 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 1,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| BC/BD-163CC5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 16.68 | not rated | not rated | not rated | not rated | not rated |
| 40 | 31.56 | 17.02 | not rated | not rated | not rated | not rated |
| 45 | 45.87 | 31.72 | 17.29 | not rated | not rated | not rated |
| 50 | 60.01 | 45.91 | 31.85 | 17.53 | not rated | not rated |
| 55 | 74.08 | 59.96 | 45.96 | 31.98 | 17.74 | not rated |
| 60 | 88.11 | 73.94 | 59.93 | 46.01 | 32.11 | 17.94 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 14.21 | not rated | not rated | not rated | not rated | not rated |
| 40 | 26.82 | 14.52 | not rated | not rated | not rated | not rated |
| 45 | 38.84 | 26.95 | 14.76 | not rated | not rated | not rated |
| 50 | 50.70 | 38.87 | 27.06 | 14.98 | not rated | not rated |
| 55 | 62.49 | 50.64 | 38.90 | 27.16 | 15.16 | not rated |
| 60 | 74.24 | 62.35 | 50.60 | 38.94 | 27.27 | 15.34 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 31.561 | 5.48 | 10.7 |
| Low speed (Y) | 26.820 | 4.66 | 8.0 |
| A | 1200 mm |
|---|---|
| B | 1200 mm |
| C | 1240 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1000 mm |
| H | 900 mm |
| I | 1190 mm |
| K | 1500 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 1500 mm |
|---|---|
| Width | 1240 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.