Product code: BC/BD-180AD5-B03 C

Heat rejection i
31.80 kW
Air flow
7,869 m³/h
Fans
1 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 7,869 m³/h
External surface 174.1 m²
Inner volume 24.0 dm³
Fin materialAluminium
Net weight 215 kg
Fans
Quantity 1
Diameter 800 mm
Speed 435 rpm
Power 300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 32.0 dB(A)
Sound power 64.0 dB(A)
Energy class C
Connections
Inlet 1 1/4"
Outlet 1 1/4"
Defrost
BC/BD-180AD5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
31.802 kW Fluid flow 5.52 m³/h Pressure drop 49.4 kPa
Heat rejection · Low speed (Y)
23.930 kW Fluid flow 4.15 m³/h Pressure drop 29.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 19.22 not rated not rated not rated not rated not rated
40 31.80 19.24 not rated not rated not rated not rated
45 44.03 31.75 19.28 not rated not rated not rated
50 56.14 43.91 31.73 19.32 not rated not rated
55 68.19 55.95 43.83 31.73 19.38 not rated
60 80.21 67.94 55.82 43.80 31.77 19.47

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 14.62 not rated not rated not rated not rated not rated
40 23.93 14.66 not rated not rated not rated not rated
45 32.95 23.92 14.70 not rated not rated not rated
50 41.88 32.90 23.92 14.75 not rated not rated
55 50.76 41.78 32.87 23.95 14.82 not rated
60 59.61 50.63 41.73 32.89 24.02 14.90

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 31.802 5.52 49.4
Low speed (Y) 23.930 4.15 29.8

Dimensions

Dimension drawing of BC/BD-180AD5-B03 C
Dimension drawing
Dimensions as drawn
A 1550 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 1300 mm
H 1200 mm
I 1190 mm
K 1850 mm
D IN 1 1/4"
D OUT 1 1/4"
Overall [mm]
Length 1850 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.