Product code: BC/BD-180AC1-B03 C

Heat rejection i
32.02 kW
Air flow
8,144 m³/h
Fans
1 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • D
    Number of fans per row: 1 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 03 — three-phase 400 V 50 Hz, 12-pole AC fan (in this series)

Data

Coil
Air flow 8,144 m³/h
External surface 164.7 m²
Inner volume 19.7 dm³
Fin materialAluminium
Net weight 208 kg
Fans
Quantity 1
Diameter 800 mm
Speed 435 rpm
Power 300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 32.0 dB(A)
Sound power 64.0 dB(A)
Energy class C
Connections
Inlet 1 1/4"
Outlet 1 1/4"
Defrost
BC/BD-180AC1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
32.017 kW Fluid flow 5.55 m³/h Pressure drop 71.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
24.459 kW Fluid flow 4.24 m³/h Pressure drop 44.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 19.25 not rated not rated not rated not rated not rated
40 32.02 19.29 not rated not rated not rated not rated
45 44.43 31.97 19.32 not rated not rated not rated
50 56.73 44.32 31.95 19.36 not rated not rated
55 68.97 56.55 44.24 31.95 19.42 not rated
60 81.18 68.72 56.42 44.20 31.99 19.50

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 14.87 not rated not rated not rated not rated not rated
40 24.46 14.90 not rated not rated not rated not rated
45 33.76 24.44 14.94 not rated not rated not rated
50 42.97 33.70 24.44 14.99 not rated not rated
55 52.14 42.87 33.67 24.47 15.05 not rated
60 61.28 52.00 42.81 33.68 24.52 15.13

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 32.017 5.55 71.3
Low speed (Y) 24.459 4.24 44.2

Dimensions

Dimension drawing of BC/BD-180AC1-B03 C
Dimension drawing
Dimensions as drawn
A 1550 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 1300 mm
H 1200 mm
I 1190 mm
K 1850 mm
D IN 1 1/4"
D OUT 1 1/4"
Overall [mm]
Length 1850 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.