BC/BD-263CD1-B01 C
61.62 kW
Defrost: None
Product code: BC/BD-180CC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 19,401 m³/h |
|---|---|
| External surface | 203.1 m² |
| Inner volume | 30.6 dm³ |
| Fin material | Aluminium |
| Net weight | 246 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-180CC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 35.91 | not rated | not rated | not rated | not rated | not rated |
| 40 | 61.60 | 36.02 | not rated | not rated | not rated | not rated |
| 45 | 86.69 | 61.55 | 36.12 | not rated | not rated | not rated |
| 50 | 111.59 | 86.51 | 61.52 | 36.22 | not rated | not rated |
| 55 | 136.40 | 111.27 | 86.36 | 61.52 | 36.33 | not rated |
| 60 | 161.16 | 135.95 | 111.01 | 86.27 | 61.56 | 36.46 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 28.59 | not rated | not rated | not rated | not rated | not rated |
| 40 | 48.58 | 28.66 | not rated | not rated | not rated | not rated |
| 45 | 68.05 | 48.51 | 28.73 | not rated | not rated | not rated |
| 50 | 87.34 | 67.86 | 48.47 | 28.80 | not rated | not rated |
| 55 | 106.56 | 87.04 | 67.71 | 48.45 | 28.88 | not rated |
| 60 | 125.73 | 106.15 | 86.80 | 67.62 | 48.47 | 28.98 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 61.600 | 10.69 | 64.1 |
| Low speed (Y) | 48.575 | 8.43 | 42.1 |
| A | 2100 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1850 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 2400 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2100 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.