BC/BD-180CC5-B01 C
61.60 kW
Defrost: None
Product code: BC/BD-2X180HA1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 36,906 m³/h |
|---|---|
| External surface | 107.2 m² |
| Inner volume | 20.8 dm³ |
| Fin material | Aluminium |
| Net weight | 295 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 83.6 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-2X180HA1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 33.76 | not rated | not rated | not rated | not rated | not rated |
| 40 | 61.57 | 34.15 | not rated | not rated | not rated | not rated |
| 45 | 88.92 | 61.87 | 34.49 | not rated | not rated | not rated |
| 50 | 116.14 | 89.16 | 62.15 | 34.80 | not rated | not rated |
| 55 | 143.30 | 116.33 | 89.39 | 62.42 | 35.09 | not rated |
| 60 | 170.44 | 143.44 | 116.52 | 89.64 | 62.69 | 35.36 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 27.91 | not rated | not rated | not rated | not rated | not rated |
| 40 | 50.65 | 28.22 | not rated | not rated | not rated | not rated |
| 45 | 72.97 | 50.88 | 28.50 | not rated | not rated | not rated |
| 50 | 95.15 | 73.13 | 51.09 | 28.75 | not rated | not rated |
| 55 | 117.28 | 95.26 | 73.29 | 51.29 | 28.98 | not rated |
| 60 | 139.38 | 117.34 | 95.38 | 73.46 | 51.50 | 29.21 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 61.574 | 10.69 | 54.6 |
| Low speed (Y) | 50.651 | 8.79 | 38.6 |
| A | 1400 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1150 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 1700 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 1400 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.