BC/BD-2X150BA1-B09 C
28.19 kW
Defrost: None
Product code: BC/BD-180HD1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 7,125 m³/h |
|---|---|
| External surface | 135.6 m² |
| Inner volume | 15.3 dm³ |
| Fin material | Aluminium |
| Net weight | 193 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 32.0 dB(A) |
|---|---|
| Sound power | 64.0 dB(A) |
| Energy class | C |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| BC/BD-180HD1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 16.72 | not rated | not rated | not rated | not rated | not rated |
| 40 | 28.24 | 16.83 | not rated | not rated | not rated | not rated |
| 45 | 39.35 | 28.27 | 16.93 | not rated | not rated | not rated |
| 50 | 50.33 | 39.33 | 28.31 | 17.03 | not rated | not rated |
| 55 | 61.25 | 50.26 | 39.33 | 28.38 | 17.14 | not rated |
| 60 | 72.13 | 61.13 | 50.22 | 39.37 | 28.48 | 17.27 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | not rated | not rated | not rated | not rated | not rated | not rated |
| 40 | not rated | not rated | not rated | not rated | not rated | not rated |
| 45 | not rated | not rated | 12.60 | not rated | not rated | not rated |
| 50 | not rated | not rated | 20.86 | 12.67 | not rated | not rated |
| 55 | not rated | not rated | 28.83 | 20.90 | 12.78 | not rated |
| 60 | not rated | not rated | 36.69 | 28.84 | 21.01 | 12.89 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 28.244 | 4.90 | 24.3 |
| Low speed (Y) | — | — | — |
| A | 1400 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1150 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 1700 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 1700 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.