Skip to Content

Dry cooler BC/BD-2X150DA1-B09 C

Dry cooler BC/BD-2X150DA1-B09 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X150DA1-B09 C

Heat rejection i
28.05 kW
Air flow
14,615 m³/h
Fans
2 × ⌀500 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 14,615 m³/h
External surface 78.4 m²
Inner volume 12.8 dm³
Fin materialAluminium
Net weight 161 kg
Fans
Quantity 2
Diameter 500 mm
Speed 1,330 rpm
Power 1,400 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 50.0 dB(A)
Sound power 82.0 dB(A)
Energy class E
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
BC/BD-2X150DA1-B09 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · Single phase
28.052 kW Fluid flow 4.87 m³/h Pressure drop 9.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Single phase

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 14.27 not rated not rated not rated not rated not rated
40 28.05 14.62 not rated not rated not rated not rated
45 41.47 28.27 14.91 not rated not rated not rated
50 54.79 41.60 28.46 15.16 not rated not rated
55 68.07 54.85 41.73 28.63 15.37 not rated
60 81.32 68.07 54.92 41.85 28.79 15.57

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 28.052 4.87 9.4

Dimensions

Dimension drawing of BC/BD-2X150DA1-B09 C
Dimension drawing
Dimensions as drawn
A 1100 mm
B 1200 mm
C 1720 mm
F 1050 mm
G 450 mm
E 900 mm
H 800 mm
I 1670 mm
K 1400 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 1400 mm
Width 1720 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.