BC/BD-t-180GB5-B03 C
27.88 kW
Defrost: None
Product code: BC/BD-2X150CB5-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 13,349 m³/h |
|---|---|
| External surface | 80.8 m² |
| Inner volume | 14.8 dm³ |
| Fin material | Aluminium |
| Net weight | 160 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 1,400 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-2X150CB5-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 13.25 | not rated | not rated | not rated | not rated | not rated |
| 40 | 27.82 | 13.84 | not rated | not rated | not rated | not rated |
| 45 | 41.60 | 28.14 | 14.31 | not rated | not rated | not rated |
| 50 | 55.23 | 41.82 | 28.42 | 14.69 | not rated | not rated |
| 55 | 68.78 | 55.37 | 42.02 | 28.67 | 15.02 | not rated |
| 60 | 82.30 | 68.86 | 55.51 | 42.21 | 28.90 | 15.31 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 27.823 | 4.83 | 5.3 |
| A | 950 mm |
|---|---|
| B | 1200 mm |
| C | 1720 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 750 mm |
| H | 650 mm |
| I | 1670 mm |
| K | 1250 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 1250 mm |
|---|---|
| Width | 1720 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.