Heat rejection i
38.28 kW
Air flow
9,147 m³/h
Fans
1 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 9,147 m³/h
External surface 226.2 m²
Inner volume 24.1 dm³
Fin materialAluminium
Net weight 241 kg
Fans
Quantity 1
Diameter 800 mm
Speed 435 rpm
Power 300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 32.0 dB(A)
Sound power 64.0 dB(A)
Energy class B
Connections
Inlet 1 1/4"
Outlet 1 1/4"
Defrost
BC/BD-180KD1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
38.277 kW Fluid flow 6.64 m³/h Pressure drop 30.4 kPa
Heat rejection · Low speed (Y)
29.007 kW Fluid flow 5.03 m³/h Pressure drop 18.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 23.11 not rated not rated not rated not rated not rated
40 38.28 23.15 not rated not rated not rated not rated
45 52.92 38.17 23.18 not rated not rated not rated
50 67.40 52.70 38.08 23.22 not rated not rated
55 81.80 67.07 52.52 38.03 23.28 not rated
60 96.15 81.36 66.80 52.40 38.03 23.35

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 17.66 not rated not rated not rated not rated not rated
40 29.01 17.68 not rated not rated not rated not rated
45 39.92 28.90 17.70 not rated not rated not rated
50 50.70 39.72 28.82 17.71 not rated not rated
55 61.42 50.42 39.56 28.75 17.75 not rated
60 72.11 61.05 50.18 39.43 28.73 17.81

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 38.277 6.64 30.4
Low speed (Y) 29.007 5.03 18.5

Dimensions

Dimension drawing of BC/BD-180KD1-B03 C
Dimension drawing
Dimensions as drawn
A 2100 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 1850 mm
H 1750 mm
I 1180 mm
K 2400 mm
D IN 1 1/4"
D OUT 1 1/4"
Overall [mm]
Length 2400 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.