BC/BD-250CC1-B09 C
38.25 kW
Defrost: None
Product code: BC/BD-180NB5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 10,664 m³/h |
|---|---|
| External surface | 208.5 m² |
| Inner volume | 27.0 dm³ |
| Fin material | Aluminium |
| Net weight | 264 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 32.0 dB(A) |
|---|---|
| Sound power | 64.0 dB(A) |
| Energy class | B |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| BC/BD-180NB5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 22.84 | not rated | not rated | not rated | not rated | not rated |
| 40 | 38.26 | 22.83 | not rated | not rated | not rated | not rated |
| 45 | 53.29 | 38.13 | 22.82 | not rated | not rated | not rated |
| 50 | 68.21 | 53.05 | 38.01 | 22.81 | not rated | not rated |
| 55 | 83.07 | 67.86 | 52.84 | 37.91 | 22.80 | not rated |
| 60 | 97.89 | 82.61 | 67.56 | 52.66 | 37.83 | 22.81 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 18.45 | not rated | not rated | not rated | not rated | not rated |
| 40 | 30.66 | 18.41 | not rated | not rated | not rated | not rated |
| 45 | 42.55 | 30.50 | 18.37 | not rated | not rated | not rated |
| 50 | 54.33 | 42.28 | 30.36 | 18.35 | not rated | not rated |
| 55 | 66.07 | 53.96 | 42.04 | 30.26 | 18.35 | not rated |
| 60 | 77.77 | 65.59 | 53.63 | 41.87 | 30.20 | 18.37 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 38.260 | 6.64 | 70.4 |
| Low speed (Y) | 30.657 | 5.32 | 47.5 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 1190 mm |
| K | 3050 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 3050 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.