BC/BD-180AB5-B01 C
41.80 kW
Defrost: None
Product code: BC/BD-180MC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 10,284 m³/h |
|---|---|
| External surface | 248.2 m² |
| Inner volume | 26.2 dm³ |
| Fin material | Aluminium |
| Net weight | 269 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 32.0 dB(A) |
|---|---|
| Sound power | 64.0 dB(A) |
| Energy class | B |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| BC/BD-180MC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 25.35 | not rated | not rated | not rated | not rated | not rated |
| 40 | 41.76 | 25.31 | not rated | not rated | not rated | not rated |
| 45 | 57.69 | 41.56 | 25.28 | not rated | not rated | not rated |
| 50 | 73.47 | 57.36 | 41.39 | 25.25 | not rated | not rated |
| 55 | 89.18 | 73.01 | 57.08 | 41.27 | 25.25 | not rated |
| 60 | 104.86 | 88.59 | 72.61 | 56.86 | 41.19 | 25.28 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 20.00 | not rated | not rated | not rated | not rated | not rated |
| 40 | 32.68 | 19.98 | not rated | not rated | not rated | not rated |
| 45 | 44.98 | 32.54 | 19.95 | not rated | not rated | not rated |
| 50 | 57.16 | 44.73 | 32.42 | 19.94 | not rated | not rated |
| 55 | 69.27 | 56.81 | 44.53 | 32.33 | 19.95 | not rated |
| 60 | 81.36 | 68.83 | 56.52 | 44.37 | 32.28 | 19.98 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 41.757 | 7.24 | 60.7 |
| Low speed (Y) | 32.683 | 5.67 | 39.2 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 1180 mm |
| K | 3050 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 3050 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.