BC/BD-180AB5-B01 C
41.80 kW
Defrost: None
Product code: BC/BD-t-250AB5-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 13,861 m³/h |
|---|---|
| External surface | 76.6 m² |
| Inner volume | 13.0 dm³ |
| Fin material | Aluminium |
| Net weight | 160 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 1,400 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 81.2 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-t-250AB5-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 24.20 | not rated | not rated | not rated | not rated | not rated |
| 40 | 41.81 | 24.28 | not rated | not rated | not rated | not rated |
| 45 | 59.03 | 41.80 | 24.36 | not rated | not rated | not rated |
| 50 | 76.13 | 58.92 | 41.78 | 24.44 | not rated | not rated |
| 55 | 93.16 | 75.92 | 58.83 | 41.79 | 24.52 | not rated |
| 60 | 110.16 | 92.87 | 75.76 | 58.78 | 41.82 | 24.61 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 41.812 | 7.26 | 88.2 |
| A | 1950 mm |
|---|---|
| B | 1220 mm |
| C | 930 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1700 mm |
| H | 800 mm |
| I | 880 mm |
| K | 2200 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 1950 mm |
|---|---|
| Width | 960 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.