BC/BD-t-380GC5-B03 C
92.09 kW
Defrost: None
Product code: BC/BD-191GC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 26,676 m³/h |
|---|---|
| External surface | 329.1 m² |
| Inner volume | 38.6 dm³ |
| Fin material | Aluminium |
| Net weight | 303 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.2 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-191GC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 54.09 | not rated | not rated | not rated | not rated | not rated |
| 40 | 92.08 | 54.19 | not rated | not rated | not rated | not rated |
| 45 | 129.12 | 91.90 | 54.27 | not rated | not rated | not rated |
| 50 | 165.84 | 128.69 | 91.75 | 54.36 | not rated | not rated |
| 55 | 202.42 | 165.17 | 128.32 | 91.66 | 54.48 | not rated |
| 60 | 238.92 | 201.51 | 164.60 | 128.06 | 91.64 | 54.63 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 43.05 | not rated | not rated | not rated | not rated | not rated |
| 40 | 72.54 | 43.12 | not rated | not rated | not rated | not rated |
| 45 | 101.21 | 72.38 | 43.18 | not rated | not rated | not rated |
| 50 | 129.62 | 100.86 | 72.25 | 43.26 | not rated | not rated |
| 55 | 157.90 | 129.07 | 100.57 | 72.18 | 43.35 | not rated |
| 60 | 186.11 | 157.17 | 128.62 | 100.37 | 72.18 | 43.49 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 92.076 | 15.98 | 85.9 |
| Low speed (Y) | 72.536 | 12.58 | 56.2 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 1190 mm |
| K | 3050 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3050 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.