BC/BD-191GC1-B04 C
92.08 kW
Defrost: None
Product code: BC/BD-t-380GC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 22,319 m³/h |
|---|---|
| External surface | 275.9 m² |
| Inner volume | 36.6 dm³ |
| Fin material | Aluminium |
| Net weight | 452 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 37.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | C |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-t-380GC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 55.80 | not rated | not rated | not rated | not rated | not rated |
| 40 | 92.09 | 55.93 | not rated | not rated | not rated | not rated |
| 45 | 127.30 | 92.01 | 56.06 | not rated | not rated | not rated |
| 50 | 162.15 | 127.05 | 91.99 | 56.23 | not rated | not rated |
| 55 | 196.84 | 161.74 | 126.90 | 92.07 | 56.45 | not rated |
| 60 | 231.44 | 196.28 | 161.48 | 126.91 | 92.26 | 56.72 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 41.83 | not rated | not rated | not rated | not rated | not rated |
| 40 | 68.21 | 41.94 | not rated | not rated | not rated | not rated |
| 45 | 93.73 | 68.16 | 42.05 | not rated | not rated | not rated |
| 50 | 118.98 | 93.57 | 68.17 | 42.20 | not rated | not rated |
| 55 | 144.10 | 118.71 | 93.50 | 68.26 | 42.39 | not rated |
| 60 | 169.15 | 143.73 | 118.57 | 93.55 | 68.45 | 42.68 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 92.088 | 15.97 | 78.5 |
| Low speed (Y) | 68.209 | 11.83 | 46.1 |
| A | 3500 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3250 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 3800 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3800 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.