BC/BD-280HD5-B01 C
92.20 kW
Defrost: None
Product code: BC/BD-380KB5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 30,365 m³/h |
|---|---|
| External surface | 344.8 m² |
| Inner volume | 44.3 dm³ |
| Fin material | Aluminium |
| Net weight | 545 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 37.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | C |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-380KB5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 53.69 | not rated | not rated | not rated | not rated | not rated |
| 40 | 92.26 | 53.87 | not rated | not rated | not rated | not rated |
| 45 | 129.89 | 92.18 | 54.02 | not rated | not rated | not rated |
| 50 | 167.23 | 129.60 | 92.12 | 54.16 | not rated | not rated |
| 55 | 204.43 | 166.72 | 129.34 | 92.09 | 54.31 | not rated |
| 60 | 241.55 | 203.72 | 166.29 | 129.17 | 92.12 | 54.49 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 43.29 | not rated | not rated | not rated | not rated | not rated |
| 40 | 73.98 | 43.47 | not rated | not rated | not rated | not rated |
| 45 | 103.82 | 73.95 | 43.63 | not rated | not rated | not rated |
| 50 | 133.41 | 103.64 | 73.94 | 43.77 | not rated | not rated |
| 55 | 162.87 | 133.07 | 103.49 | 73.96 | 43.93 | not rated |
| 60 | 192.27 | 162.39 | 132.81 | 103.42 | 74.04 | 44.12 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 92.263 | 16.01 | 42.1 |
| Low speed (Y) | 73.975 | 12.84 | 28.3 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1750 mm |
| I | 1180 mm |
| K | 5900 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 5900 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.