BC/BD-380KB5-B03 C
92.26 kW
Defrost: None
Product code: BC/BD-363CD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 23,318 m³/h |
|---|---|
| External surface | 463.3 m² |
| Inner volume | 53.7 dm³ |
| Fin material | Aluminium |
| Net weight | 385 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 79.6 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-363CD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 54.52 | not rated | not rated | not rated | not rated | not rated |
| 40 | 92.40 | 54.74 | not rated | not rated | not rated | not rated |
| 45 | 128.99 | 92.29 | 54.95 | not rated | not rated | not rated |
| 50 | 165.14 | 128.61 | 92.22 | 55.14 | not rated | not rated |
| 55 | 201.09 | 164.52 | 128.32 | 92.22 | 55.37 | not rated |
| 60 | 236.93 | 200.23 | 164.02 | 128.16 | 92.33 | 55.65 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 92.401 | 16.03 | 26.2 |
| A | 3000 mm |
|---|---|
| B | 1200 mm |
| C | 1240 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 1190 mm |
| K | 3300 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3300 mm |
|---|---|
| Width | 1240 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.