BC/BD-2X350CB5-B09 C
92.63 kW
Defrost: None
Product code: BC/BD-t-2x180LC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 20,263 m³/h |
|---|---|
| External surface | 415.0 m² |
| Inner volume | 57.5 dm³ |
| Fin material | Aluminium |
| Net weight | 461 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 35.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | B |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-t-2x180LC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 57.65 | not rated | not rated | not rated | not rated | not rated |
| 40 | 92.56 | 57.42 | not rated | not rated | not rated | not rated |
| 45 | 126.35 | 91.94 | 57.23 | not rated | not rated | not rated |
| 50 | 159.79 | 125.38 | 91.40 | 57.08 | not rated | not rated |
| 55 | 193.08 | 158.50 | 124.56 | 90.99 | 57.01 | not rated |
| 60 | 226.27 | 191.46 | 157.38 | 123.90 | 90.71 | 57.02 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 44.44 | not rated | not rated | not rated | not rated | not rated |
| 40 | 70.66 | 44.29 | not rated | not rated | not rated | not rated |
| 45 | 96.02 | 70.23 | 44.17 | not rated | not rated | not rated |
| 50 | 121.12 | 95.35 | 69.87 | 44.09 | not rated | not rated |
| 55 | 146.10 | 120.23 | 94.79 | 69.60 | 44.06 | not rated |
| 60 | 171.02 | 144.99 | 119.48 | 94.37 | 69.45 | 44.11 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 92.555 | 16.05 | 60.6 |
| Low speed (Y) | 70.656 | 12.26 | 37.4 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 2260 mm |
| K | 3050 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3050 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.