BC/BD-t-263AB5-B01 C
54.26 kW
Defrost: None
Product code: BC/BD-191KB1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 24,194 m³/h |
|---|---|
| External surface | 108.6 m² |
| Inner volume | 13.9 dm³ |
| Fin material | Aluminium |
| Net weight | 206 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-191KB1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 29.72 | not rated | not rated | not rated | not rated | not rated |
| 40 | 54.30 | 30.10 | not rated | not rated | not rated | not rated |
| 45 | 78.34 | 54.54 | 30.42 | not rated | not rated | not rated |
| 50 | 102.22 | 78.49 | 54.77 | 30.71 | not rated | not rated |
| 55 | 126.03 | 102.29 | 78.64 | 54.98 | 30.98 | not rated |
| 60 | 149.81 | 126.02 | 102.37 | 78.81 | 55.21 | 31.24 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 23.94 | not rated | not rated | not rated | not rated | not rated |
| 40 | 43.48 | 24.26 | not rated | not rated | not rated | not rated |
| 45 | 62.50 | 43.68 | 24.53 | not rated | not rated | not rated |
| 50 | 81.37 | 62.62 | 43.86 | 24.77 | not rated | not rated |
| 55 | 100.17 | 81.42 | 62.74 | 44.04 | 25.00 | not rated |
| 60 | 118.93 | 100.15 | 81.49 | 62.88 | 44.23 | 25.23 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 54.301 | 9.42 | 35.3 |
| Low speed (Y) | 43.483 | 7.55 | 23.7 |
| A | 1750 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1500 mm |
| H | 1400 mm |
| I | 1180 mm |
| K | 2050 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2050 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.