Skip to Content

Dry cooler BC/BD-2x180HD5-B03 C

Dry cooler BC/BD-2x180HD5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x180HD5-B03 C

Heat rejection i
54.20 kW
Air flow
14,710 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 14,710 m³/h
External surface 226.9 m²
Inner volume 36.2 dm³
Fin materialAluminium
Net weight 337 kg
Fans
Quantity 2
Diameter 800 mm
Speed 435 rpm
Power 600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 35.0 dB(A)
Sound power 67.0 dB(A)
Energy class C
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-2x180HD5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
54.200 kW Fluid flow 9.41 m³/h Pressure drop 21.5 kPa
Heat rejection · Low speed (Y)
40.547 kW Fluid flow 7.03 m³/h Pressure drop 12.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 31.75 not rated not rated not rated not rated not rated
40 54.20 31.98 not rated not rated not rated not rated
45 75.89 54.28 32.19 not rated not rated not rated
50 97.34 75.88 54.39 32.40 not rated not rated
55 118.69 97.25 75.92 54.53 32.62 not rated
60 139.98 118.52 97.24 76.03 54.73 32.87

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 23.92 not rated not rated not rated not rated not rated
40 40.55 24.13 not rated not rated not rated not rated
45 56.51 40.63 24.31 not rated not rated not rated
50 72.27 56.52 40.72 24.50 not rated not rated
55 87.94 72.22 56.57 40.85 24.68 not rated
60 103.56 87.84 72.24 56.68 41.03 24.90

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 54.200 9.41 21.5
Low speed (Y) 40.547 7.03 12.8

Dimensions

Dimension drawing of BC/BD-2x180HD5-B03 C
Dimension drawing
Dimensions as drawn
A 1400 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 1150 mm
H 1050 mm
I 2260 mm
K 1700 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 1700 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.