BC/BD-t-163AC5-B01 C
30.54 kW
Defrost: None
Product code: BC/BD-250DA1-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 14,615 m³/h |
|---|---|
| External surface | 78.2 m² |
| Inner volume | 10.0 dm³ |
| Fin material | Aluminium |
| Net weight | 167 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 1,400 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 82.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-250DA1-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 16.97 | not rated | not rated | not rated | not rated | not rated |
| 40 | 30.53 | 17.11 | not rated | not rated | not rated | not rated |
| 45 | 43.85 | 30.60 | 17.23 | not rated | not rated | not rated |
| 50 | 57.11 | 43.87 | 30.66 | 17.33 | not rated | not rated |
| 55 | 70.33 | 57.07 | 43.89 | 30.73 | 17.43 | not rated |
| 60 | 83.54 | 70.24 | 57.04 | 43.91 | 30.80 | 17.53 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 30.525 | 5.30 | 56.1 |
| A | 1900 mm |
|---|---|
| B | 1200 mm |
| C | 920 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1700 mm |
| H | 800 mm |
| I | 870 mm |
| K | 2200 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2200 mm |
|---|---|
| Width | 920 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.